[Fort Pierce (Stonewall) 22-A]
Number: Grading-37235

Drawing of Record Submitted 7/16/2007
Electronic Drawing 7/16/2007
Final Grading Report 8/9/2007 revised
Date Scheduled
BUILDING PERMIT RELEASE APPROVALS
Power
Water
Wastewater
Engineering
City Development Engineer
Landscaping
FINAL INSPECTION RELEASE APPROVALS
Power
Water 7/26/2007..corrections required per Carson Tait.. The backflow assembly needs to be raised. The installation criteria for a pub states that it is to be installed 12" above the highest outlet. It also needs to be tested and tagged after it has been installed correctly. 7/31/07 corrections required per Darrin Judd - PVB not 12" above highest outlet. Also needs to be tested and tagged. 8/17/2007 Approved per Carson Tait
Wastewater 7/26/2007..corrections required per Carson Tait.. The backflow assembly needs to be raised. The installation criteria for a pub states that it is to be installed 12" above the highest outlet. It also needs to be tested and tagged after it has been installed correctly. 7/31/07 corrections required per Darrin Judd - PVB not 12" above highest outlet. Also needs to be tested and tagged. 8/17/2007 Approved per Carson Tait
Engineering 7/30/2007 Corrections required per Brandon Wirght.. No grading report on testing 8/9/2007 Approved per Brandon W.
City Development Engineer Corrections required per Cathy H...Provide Elec drawing of record in Autocad format, showing all utilities,dimensions, location, etc. 7/26/07 corrections required per Cathy H. Electronic dwg of record needs to be put on city HCN system.
Landscaping 7/26/07 approved per Ken B.
    