Drawing of Record Submitted |
7/16/2007 |
Electronic Drawing |
7/16/2007 |
Final Grading Report |
8/9/2007 revised |
Date Scheduled |
|
BUILDING PERMIT RELEASE APPROVALS |
Power |
|
Water |
|
Wastewater |
|
Engineering |
|
City Development Engineer |
|
Landscaping |
|
FINAL INSPECTION RELEASE APPROVALS |
Power |
|
Water |
7/26/2007..corrections required per Carson Tait.. The backflow assembly needs to be raised. The installation criteria for a pub states that it is to be installed 12" above the highest outlet. It also needs to be tested and tagged after it has been installed correctly.
7/31/07 corrections required per Darrin Judd - PVB not 12" above highest outlet. Also needs to be tested and tagged.
8/17/2007 Approved per Carson Tait |
Wastewater |
7/26/2007..corrections required per Carson Tait.. The backflow assembly needs to be raised. The installation criteria for a pub states that it is to be installed 12" above the highest outlet. It also needs to be tested and tagged after it has been installed correctly.
7/31/07 corrections required per Darrin Judd - PVB not 12" above highest outlet. Also needs to be tested and tagged.
8/17/2007 Approved per Carson Tait |
Engineering |
7/30/2007 Corrections required per Brandon Wirght.. No grading report on testing
8/9/2007 Approved per Brandon W. |
City Development Engineer |
Corrections required per Cathy H...Provide Elec drawing of record in Autocad format, showing all utilities,dimensions, location, etc.
7/26/07 corrections required per Cathy H. Electronic dwg of record needs to be put on city HCN system. |
Landscaping |
7/26/07 approved per Ken B. |
| |
General Comments: |
|