Drawing of Record Submitted |
2/15/2008 |
Electronic Drawing |
2/15/2008 |
Final Grading Report |
2/19/2008 |
Date Scheduled |
2/20/2008 |
BUILDING PERMIT RELEASE APPROVALS |
Power |
|
Water |
|
Wastewater |
|
Engineering |
|
City Development Engineer |
|
Landscaping |
|
FINAL INSPECTION RELEASE APPROVALS |
Power |
|
Water |
2/25/2008 Corrections required per Carson Tait.. Need to replace the valve collar on the West Side (3 valves).Is the hydrant on the West Side temporary or permanent? Locate wire does not trace through. The City spec calls for #4 bar in the meter boxes.
12/02/2013 Approved per Kevin Condie |
Wastewater |
2/25/2008 Corrections required per Carson Tait.. Need to replace the valve collar on the West Side (3 valves).Is the hydrant on the West Side temporary or permanent? Locate wire does not trace through. The City spec calls for #4 bar in the meter boxes.
12/02/2013 Approved per Kevin Condie |
Engineering |
2/20/2008 Approved per Carlos Robles |
City Development Engineer |
2/20/2008 Corrections required per Cathy H.. Electronic Dwg of record-temp. retention basin needs to be removed, storm drain pipe needs to be labled with type,size,slope, length etc., and drainage system needs to show how it is connected from cul-de-sac to rest of the system.
12/31/2013.. Approved per Wes Jenkins |
Landscaping |
2/20/2008 Approved per Ken Bricker.. |
| |
General Comments: |
|