[Fort Pierce #127 Mountainlands Pipe Supply]
Number: Grading-40409

Drawing of Record Submitted 3/13/2009..revised 3/26/2009
Electronic Drawing 3/13/2009..revised 3/26/2009
Final Grading Report 3/12/2009
Date Scheduled 3/16/2009
BUILDING PERMIT RELEASE APPROVALS
Power
Water
Wastewater
Engineering
City Development Engineer
Landscaping
FINAL INSPECTION RELEASE APPROVALS
Power
Water 3/18/2009 Corrections required per Carson Tait..Tracer wire coming out of valve cans on North west side of building won't trace going north to end of stub,wire to fire riser will only work form inside building out to can. need to dig up and repair. Need to have the Rip back flow assembly at the meter tested and tagged. Need a hose bib vacuum breaker on the hose bib at the R-p 3/25/2009 Corrections required per Carson Tait.. Marking/locate wire test failed. Need to dig up at the valve collar and repair the short to ground. 4/1/2009 Corrections required per Carson Tait..Checked 3/26-27 not ready.. checked 3/30 not ready.. Checked 3/31 & 4/1 equipment parked over the valves,could not complete the inspection. 4/15/2009 Corrections required per Carson Tait: The wires in the newly poured concrete valve collar have been cut because the wires were placed too high in the riser. This placement allowed the lid to cut the wires and make a ground through the riser. Need to do it over. 4/23/2009 Approved per Carson Tait 2/26/2010 Approved per Kevin Condie.. 1 year warranty
Wastewater 3/18/2009 Corrections required per Carson Tait..Tracer wire coming out of valve cans on North west side of building won't trace going north to end of stub,wire to fire riser will only work form inside building out to can. need to dig up and repair. Need to have the Rip back flow assembly at the meter tested and tagged. Need a hose bib vacuum breaker on the hose bib at the R-p 3/25/2009 Corrections required per Carson Tait.. Marking/locate wire test failed. Need to dig up at the valve collar and repair the short to ground. 4/1/2009 Corrections required per Carson Tait..Checked 3/26-27 not ready.. checked 3/30 not ready.. Checked 3/31 & 4/1 equipment parked over the valves,could not complete the inspection. 4/15/2009 Corrections required per Carson Tait: The wires in the newly poured concrete valve collar have been cut because the wires were placed too high in the riser. This placement allowed the lid to cut the wires and make a ground through the riser. Need to do it over. 4/23/2009 Approved per Carson Tait 2/26/2010 Approved per Kevin Condie.. 1 year warranty
Engineering 3/18/2009 Approved per Brandon Wright 2/8/10 - 1 year warranty - approved per Brandon W.
City Development Engineer 3/18/2009 Approved per Cathy H.. Electronic Dwg of record- ok 2/3/10 - 1 year warranty (check L/S only) - approved per Ken B.
Landscaping 3/17/2009 Approved per Pam Klotz..remove nursery stakes from trees.. Pam Klotz 703-0941 2/3/10 - 1 year warranty (check L/S only) - approved per Ken B.
    
General Comments: